29.7
理想的 Y-Y 变压器通过中性阻抗接地,在受到平衡正序或负序电流时,其标幺序网络与单相理想变压器类似。这些电流不会产生中性电流及其相关的电压降。
零序电流的幅值和相位相同,会产生中性电流,导致中性阻抗和低压绕组两端的电压下降。如果变压器的中性线不接地,零序电流就无法流向地面,但仍可以在绕组内循环。
…
当流过平衡的正序或负序电流时,通过中性点阻抗接地的理想Y-Y变压器的标幺值序网与单相变压器相似,此时中性点电流和电压降可忽略不计。
三个相位的零序电流合并形成中性线电流,导致中性线阻抗上产生电压降,并影响低压绕组的电压。
实际的 Y-Y 变压器在其标幺值序网中包含外部阻抗。每一相均表示一个与励磁电感并联的铁芯损耗电阻。
这些变压器的正序和负序阻抗的标幺值相同,而零序网络则取决于中性点阻抗。
Delta-delta 变压器具有相同的正序和负序网络,其标幺值阻抗与绕组连接方式无关。
通过使用相同的基准容量(S-base)和成比例的电压基准,将三个相似的单相变压器连接起来,从而为三相三绕组变压器建立每单位序列模型。
在零序网络中,高压侧连接方式取决于高压绕组的配置。
View the full transcript and gain access to JoVE Core videos
Q1: How do positive and negative-sequence currents behave in an ideal Y-Y transformer with grounded neutral?
In an ideal Y-Y transformer grounded via neutral impedances, balanced positive or negative-sequence currents flow without producing neutral currents or voltage drops. The per-unit sequence networks resemble those of a single-phase transformer. This symmetry simplifies analysis because positive and negative-sequence impedances are identical, allowing straightforward modeling of balanced fault conditions.
Q2: What happens to zero-sequence currents in a Y-Y transformer with an ungrounded neutral?
Zero-sequence currents cannot flow to ground through an ungrounded neutral but can still circulate within the windings. These identical-magnitude, in-phase currents combine to form a neutral current, causing voltage drops across the neutral impedance and affecting the low-voltage winding voltage. This circulation path allows zero-sequence analysis even without a ground connection.
Q3: How do practical Y-Y transformers differ from ideal transformers in per-unit sequence modeling?
Practical Y-Y transformers incorporate external impedances in their per-unit sequence networks. Shunt branches represent balanced-Y impedance loads, with each phase containing a core loss resistor in parallel with magnetizing inductance. Despite these additions, positive and negative-sequence impedances remain identical, while zero-sequence networks depend on neutral impedance configuration.
Q4: What is the relationship between positive and negative-sequence impedances in delta-delta transformers?
Delta-delta transformers have identical positive and negative-sequence networks with per-unit impedances independent of winding connections. This consistency simplifies fault analysis since both sequence types experience the same impedance. However, practical transformers may show variations depending on actual winding configuration and core design.
Q5: How are three-phase, three-winding transformers modeled using per-unit sequence networks?
Three-phase, three-winding transformers are modeled by connecting three identical single-phase transformers using a common S-base for all terminals and proportional voltage bases for each winding. This approach ensures consistent per-unit representation across all three phases and windings, enabling accurate analysis of sequence currents and voltages throughout the transformer.
Q6: Why does the high-voltage winding configuration matter in zero-sequence network analysis?
In the general zero-sequence network, the high-voltage winding configuration dictates the high-voltage connection and determines how zero-sequence currents flow through the transformer. Different configurations—such as grounded or ungrounded Y, or delta—create different zero-sequence paths and impedances, directly affecting fault current distribution and voltage response during unsymmetrical faults.
Q7: How do per-unit sequence models support analysis of unsymmetrical faults in power systems?
Per-unit sequence models decompose unsymmetrical faults into positive, negative, and zero-sequence components, each with defined impedances. By analyzing how sequence networks of rotating machines and transformers interact during faults, engineers can calculate fault currents and voltages. This approach enables proper circuit breaker and fuse selection for system protection.