31.2
The Synchronous Machine Model is crucial in transient stability studies.
It represents a synchronous machine with a constant internal voltage behind its direct axis transient reactance under balanced three-phase positive-sequence conditions, constant excitation, and no losses or saturation.
Here, each generator connects to a system composed of transmission lines, transformers, loads, and other machines represented by an infinite bus behind system reactance.
Consider a synchronous generator connected to a grid or infinite bus with constant voltage magnitude, phase, and frequency. Its power is a sinusoidal function of the machine power angle.
During transients, internal and bus voltages are considered constant for power calculations.
The Equal-Area Criterion is used when a step change occurs in mechanical power. The rotor accelerates due to inertia, overshooting its final steady-state point before stabilizing due to damping from mechanical and electrical losses.
The Equal-Area Criterion applies to a single machine connected to an infinite bus or two interconnected machines.
For multi-machine systems, each machine's nonlinear swing equation is solved using numerical integration to determine stability and maximum power angle.
Het Synchronous Machine Model is een fundamenteel hulpmiddel bij het analyseren en waarborgen van de transiënte stabiliteit van energiesystemen. Dit m…
Copyright © 2026 MyJoVE Corporation. Alle rechten voorbehouden.