1. Make sure the three-phase disconnect switch is off.
2. Check that the VARIAC is at 0%.
3. Perform the following connections at the machine and VARIAC terminals:
4. Press the "Lo/Re" button once to put the drive in local mode - the redlight on that button should turn on.
5. Check that the drive parameters are the same as those shown in Table 1.
6. To perform basic voltage, current, and frequency measurements:
7. To set a different output frequency, and thus set a different motor speed since speed and electrical frequency are proportional:
8. Set the frequency to 10 Hz.
9. Note that if the drive overloads or faults: Press the red "Stop" button, and then press the > (right arrow/reset) button.

Table 1: Main VFD Settings
Source: Ali Bazzi, Department of Electrical Engineering, University of Connecticut, Storrs, CT.
Variable frequency drives (VFDs) are a type of adjusta…
Chapters in this video
0:06
Overview
1:20
Principles of Variable Frequency Drives
6:05
Configuring a Variable Frequency Drive Controller
8:56
Applications
10:06
Summary